FIRSTO® by Beele Engineering BV
T: +31(0)543 461629
F: +31(0)543 461786
E:
I:
|
|
The casing of the FIRSTO
firestop is secured to the wall making use of a fire resistant FRR/HF
packing.
The underside and lateral sides of the FIRSTO casing are provided
with ACTIFOAM sheets. The first layer of cables is spread out on the
bottom layer.
|

|
|
The
cables are spaced apart by means of separation profiles.
Next, one or more ACTIFOAM sheets are placed on top of the first
cable layer.
Then the second layer of cables is spaced apart in the same way. |
 |
The
space remaining after all the cables have been packed with
ACTIFOAM foam rubber is filled up with ACTIFOAM sheets.
Finally, the lid is secured on the firestop casing. |

|
 |
If a
watertight or airtight seal is needed, we recommend applying a
thin coat of our FIWA sealant over the exposed edge of the
ACTIFOAM sheets. This non-intumescent silicon-based elastomer
provides a durable weather-resistant seal that is unaffected by
most chemical environments. |
Download
the summary of the installation instructions for the FIRSTO
firestop .
|
|